Wiring
instructions for GFR-3 |
|
|
|
-
All load cables, including the neutral (if used), should pass
through the window of the sensor.
-
All wiring to the GFR-3 Ground Relay System should be rated
600V. Use a minimum of number 14 AWG. Ensure that safety requirements
are met as per your local electrical code.
-
The conductors from the Sensor to the GFR-3 Relay carry very low
current. Extra care should be taken to keep this wiring at least
10 cm away from the power conductors. The wiring should be set
up as a twisted pair and grounded at one point only. If the length
of wiring exceeds 1.5 m, the twisted pair should be shielded and
grounded as shown below.
|
|